CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
1.6.5 Optional Equipment
1.6.5.1 Humidistat/Dehumidistat
As an option for systems utilizing an A-Tech 1.1 or A-
Tech 1.2 thermostat, a room mounted humidistat and/
or dehumidistat may be shipped loose for field installa-
tion. Each device has an adjustment dial on the front
where the operator selects the desired setpoint.
If an optional humidifier is selected, the humidistat is
included to control it’s operation. The humidistat
controls the humidifier’s operation independant of the
control thermostat however, the blower must be on for
the humidifier to operate.
If the heat/reheat option is selected, a dehumidistat is
provided. If room humidity rises above setpoint when the
demand for cooling is satisfied, the dehumidistat signals
the compessor to turn on, removing humidity. At the same
time, the heater(s) are turned on to offset the cooling effect
thus maintaining the temperature of the space to be
conditioned. Refer to the electrical drawing supplied with
your unit for details specific to your system.
1.6.5.2 Temperature/Humidity Sensor
As a standard for systems utilizing C-Tech 10, A-Tech
20 or C6000 controllers, a temperature/humidity (T/H)
sensor is typically factory mounted in the return air
stream for room air control. As an option, the T/H
sensor may be shipped loose for field installation.
Refer to the electrical drawing supplied with your unit
for details specific to your system.
1.6.5.3 Heaters
The precision A/C unit may incorporate heaters for
reheating the supply air as required to offset the
sensible cooling of the system during the dehumidifi-
cation cycle and for the automatic heating mode.
Heaters are typically placed in the supply air stream
after the cooling coil to heat the supply air.
Nichrome wire electric resistance heating elements
may be factory installed in the supply airstream.
Electric heating elements are protected with line
fuses, thermal fuse links and over-temperature safety
switches which automatically reset.
As an option, hot water reheat may be selected for
sensible reheating during the dehumidification cycle. A
hot water heating coil may be factory installed in the
supply air stream. A valve is provided to control the
flow of hot water through the coil to maintain the
correct reheat temperature.
1-7
Hot Gas Reheat may be selected (for
CeilAiR
units
with DX cooling only) for automtic sensible reheating
during the dehumidification cycle. Hot compressor
discharge gas is diverted from the condenser to a hot
gas heating coil mounted in the supply air stream.
1.6.5.4 Humidifier
CeilAiR
systems may utilize an optional electrode
steam humidifier. The humidifier is factory installed
inside the air conditioner and includes fill and drain
valves and associated piping. Operation of the
humidifier’s fill and drain cycles is based on water
conductivity and is maintained by the humidifier
controller. An operating manual for the humidifier is
provided under separate cover. Refer to that manual for
detailed information on operation of the humidifier.
1.6.5.5 Condensate Pump
An optional factory installed condensate pump may be
provided. The pump automatically eliminates conden-
sate and humidifier flush water (if applicable) from the
drain pan. Should an overflow occur, an internal
overflow safety switch is wired to the system controller
to automatically shut down the precision A/C system.
1.6.5.6 Smoke Detector
Optionally mounted in the return air stream, a photo-
electric smoke detector is used to sense the presence
of smoke and signal the controller when a smoke
alarm condition exists and shuts down the air condi-
tioner.
1.6.5.7 Firestat
Optionally mounted in the return air stream, a fire
detector senses high retun air temperature and signals
the controller when a fire alarm condition exists and
shuts down the air conditioner.
1.6.5.8 Water Detector
As an option, SATS offers spot type or strip/cable type
water detectors. Upon sensing a water leak, the water
detector control circuit will signal the A/C system
controller of the alarm condition and shut down the air
conditioner’s water producing operation.